; PowerFlex 525 DL-2 Top-level Configuration ;------------------------------------------------------------------- ; AN-X DRV Top-level configuration file ; Options, Profibus Baud & Slave and mappings. ; See: qtsusa.com/dist/AN-X3/PB/PBS-DRV/Training/FormatOf_AnxPbsDrvCfg.txt ; for configuration details ; Template links to: ; - EthDev Ethernet/IP device parameters (may be included in EthDef) ; - EthDef Ethernet/IP mapping tags, may include device parameters ; - PbsDef Profibus Slave mappings to Ethernet/IP tags ; *** Note: Although Template files have a csv extension, they MUST be ; edited with a text editor and commas are not required! ; Existing Profibus IO sizes and DeviceIDs can be captured using the ; "Profibus DP Auto Config" function in the AN-X3-PBS-HMI firmware. ;------------------------------------------------------------------- BaudRate 12m FaultPbSlave ; Fault Profibus Slave Node if Ethernet/IP Target is not active ; Node ILen OLen DeviceID PbSlave 11 8 8 0x08a5 ; Replace Node, Lens and DeviceID with Profibus drive being replaced ; This example is 0 PKW, 4 PZD PKWLen 0 ; PKW Header Int Len (0 or 4), PZD DataOffset: 0 PKW, 4 PZD Name "PF525_198" ; Replace with a name appropriate to the process IpAddr 10.10.0.198 ; Ethernet/IP drive IP address RPI 10 ; 1 to 750ms, as supported by Ethernet/IP drive Template, EthDef_PF525_DL-2 ; include file that defines drive Ethernet tags Template, PbsDef_PF525_DL-2 ; include file that maps Profibus I/O to Ethernet/IP tags EndPbSlave