;QTS AN-X2 MOD RIO Scan Configuration Utility ;Copyright (c) 2005-2016 Quest Technical Solutions ;Auto Config Ethernet/IP File Ver4.1.14 ;ScanModProg ;RedundEna,MOD_A_ ; Enable Redundant configuration and specify Redund Prefix ;LongInp ; Force drops to send all inputs on every scan LedModeDebug ; Not ODVA Compliant, but useful for debugging network ClxName,AnxModMas ClxPrefix,MOD_ ClxSlot,0 DataOutput ; , Outputs from ControlLogix ; 0,RedundCtl ; Len=1 Redundancy Control 1,d4s5,d04s5_Out,; Len= 2 DDO_353_00 DC OUT 24V 4x8 3,d4s7,d04s7_Out,; Len= 4 ACO_020_00 AN OUT 4CH CURR 7,d5s3,d05s3_Out,; Len= 4 B872 ANALG 4 CH O B872 11,d5s4,d05s4_Out,; Len= 1 B804 16-OUT B804 DataInput ; , Inputs to ControlLogix 0,DropErr ; *** Always Map to Ofs 0 Since Logix will set to all 1's if AN-X Connection is lost 2,d4s4,d04s4_Inp,; Len= 2 DDI_353_00 DC IN 24V 4x8 Sink 4,d4s6,d04s6_Inp,; Len= 9 ACI_030_00 AN IN 8CH UNIPOLAR 13,d5s2,d05s2_Inp,; Len= 4 B863 REG 4 CH IN B863 ;The following lines map Diagnostics into ClxSlot 15 ClxSlot,15 DataOutput 0,DiagCtl ; Len=1 Set Bit 0 to clear diagnostic counters DataInput ; , Inputs to ControlLogix 0,DiagCtrs, ; Len=10 S908 Diagnostic Counters 10,ScanSts ; Len=5 S908 Scan Status 15,d4ModHlth,; Len=5 20,d5ModHlth,; Len=5 ;Module Status Byte for Quantum Only 25,d4ModSts, 4 ; ;ControlLogix Connection Statistics 30,ConnStats0, ; Len=10 40,ConnStats15, ; Len=10